咨询热线:18991102478(微信同号)李工 QQ:2089330467
美国UE 100系列差压开关技术参数:
型号 可调整设定范围 死区 zui大压力 耐压**
Model Adjustable Set Point Range Deadband Over Range Proof
psi bar psi bar psi bar psi bar
Buna N diaphragm and sealing diaphragms with aluminum 1/8” NPT (female) pressure connections
540 0.2 to 7 “wcd 0,5 to 17,4 mbar 0.05 to 0,6 “wc 0,1 to 1,5 mbar 30 ”Hg to 200 -1 to 13,8 400 27,6
541 1 to 20 “wcd 2,5 to 49,8 mbar 0.1 to 1.0 “wc 0.2 to 2,5 mbar 30 ”Hg to 200 -1 to 13,8 400 27,6
542 5 to 50 “wcd 12,4 to 124,5 mbar 0.2 to 2.5 “wc 0,5 to 6,2 mbar 30 ”Hg to 200 -1 to 13,8 400 27,6
543 10 to 200 “wcd 24,9 to 497,8 mbar 0.5 to 8 “wc 1,2 to 19,9 mbar 30 ”Hg to 200 -1 to 13,8 400 27,6
544 2 to 20 0,1 to 1,4 0.1 to 1.3 6,9 to 89,6 mbar 30 ”Hg to 1200 -1 to 82,7 2500 172,4
545 5 to 50 0,3 to 3,4 0.2 to 2.2 13,8 mbar to 0,1 bar 30 ”Hg to 1200 -1 to 82,7 2500 172,4
546 10 to 125 0,7 to 8,6 0.4 to 5.0 27,6 mbar to 0,3 bar 30 ”Hg to 1200 -1 to 82,7 2500 172,4
547 50 to 250 3,4 to 17,2 0.8 to 10 0,1 to 0,7 30 ”Hg to 1200 -1 to 82,7 2500 172,4
548 100 to 500 6,9 to 34,5 2. 0 to 15 0,1 to 1,0 30 ”Hg to 1200 -1 to 82,7 2500 172,4
美国UE 100系列差压开关在使用中常见的几大故障:
压差开关测压不准确,或者表跳动大发生原因和排除方法如下:
a、油液中污物将压差开关和压力表的阻尼孔(一般为φ0.8~1.0mm堵塞。压力表指针会产生跳动大、动作愚钝的现象,影响丈量值的准确性。此时可拆开压力表进行清洗,用φ0.5mm钢并注意油液的清洁度,丝穿通阻尼孔,各測量点的压力靠间隙密封隔开,当阀芯与阀体孔配合间隙较大。
b、在临时使用后。无法严格关闭,内泄漏量大;X型压力开关因内泄漏特别大,则測压无法进行。
c、为调节阻尼器(阀芯前端为锥面节流)当调节过大时。会引起压力表指针摆动,测出的压力值不准确,而且表动作缓慢。此时应适当调小阻尼开口,节流锥可在外圆磨床上校正修磨锥面。
e、压力表装的位置不对。笔者曾发现有人将压力表装在溢流阀的遥控孔处。由于压力表的波登管中有残留空气。压力表的压力跳动便不可避免。将压力表这种现象立刻消失。改装在其他能測量泵压力的地方。
美国UE 100系列差压开关的调试方法:
1. 将万用表接到输出导线上;
2. 旋下控制器顶上的螺钉;
3. 将正负压差加至0.15MPa,此值可从标准压力计中读出;
4. 松开紧定螺钉;
5. 用一字扳手,顺时针旋动设定值调节螺内六角槽,使设定值有小变大,直至开关触点在0.15MPa处切换;
6. 调节校验台压力在0.6MPa上下来回变化,检验压力下降时是否是0.15Mpa,此值即为要设定的下切换值。其对应的上切换值在0.16-0.17MPa之间;
7. 旋紧紧定螺钉。
8. 调试完毕。